See the drain kit for internal actual installation instructions.
Ptac wall sleeve installation instructions.
The wall sleeve be installed a minimum of 36 from the ceiling.
In applications where the drain holes on the ptac wall sleeve are not exposed beyond the wall an internal drain system is recommended.
All wall and window wall installations must provide for proper drainage.
To ensure proper airflow and filter removal it is recom mended installation of the wall sleeve be a minimum of 36 from the ceiling.
If the sleeve projects more than 8 into the room a sub base or other means of support must be used.
Tools required by.
Failure to install and maintain our product according to these instructions may void any product warranty.
16 24 28 and 31 deep cases are available for thicker walls.
Page 3 pre installation considerations before proceeding with the sleeve installation ensure the following guidelines for locating the wall opening and sleeve are met.
All wall and window wall installations must provide for proper drainage.
For sunrooms and modular buildings adhere to their installation instructions for supporting and sealing sleeve to their frames.
Wall case must be sealed caulked to outside wall on all four 4 sides.
Prepare and install the new wall sleeve according to the instructions below.
While the dimensions may appear to be incompatible the 2 devices should fit properly.
For new installs ensure the wall is properly framed to support the weight and dimensions of the wall sleeve and air conditioner.
Figure 4 minimum interior and exterior note.
The wall sleeve must be fastened securely before installing the air conditioner unit.
Insure that the unit is only installed in a wall structurally adequate to support the unit including the sleeve chassis and accessories.
The sleeve will fit flush in the wall extending outside the structure.
The air conditioner will slide into the sleeve but is not flush with the wall.
This information might be about you your preferences or your device and is mostly used to make the site work as you expect it to.
There is a portion of the air conditioner which extends a few inches back into the room.
In applications where the drain holes on the ptac wall sleeve are not exposed beyond the wall an internal drain system is recommended.
Wall case should be sealed caulked to the inside wall on all four 4 sides.
When you visit any website it may store or retrieve information on your browser mostly in the form of cookies.
For sunrooms and modular buildings adhere to their installation instructions for supporting and sealing sleeve to their frames.
Inches mm inches mm inches mm wall sleeve only 3 75 0 0 0 0 subbase kit 3 75 3 1 4 85 2 3 4 70.
Wall sleeve installation 920 087 04 8 05 wall sleeve installation instructions pdxws note.
Consult a licensed contractor as needed.